Cold Storage Room Capacity 5 Ton
Description:
1.1. Technical Specifications & Cold Storage Room Support
Cold storage room is a storage unit to keep the stored ingredients fresh and the cooling time is in accordance with the needs of the stored product, namely ice cubes.
1.1.1. Cold Storage Operating Conditions
1.1.1.1. Total room dimensions: W x W x H = 3,000 x 3,000 x 2,300 mm
1.1.1.2. Capacity: 5 tons (*depending on the layout and layout of the goods)
1.1.1.3. Refigerant : Freon R404A / R22
1.1.1.4. Room temperature : -18 to -20 0C
1.1.1.5. Evaporation temperature (SST) : -25 0C
1.1.1.6. Condensation temperature (SDT): 40 0C
1.1.1.7. Digital Temperature Control
1.1.1.8. Initial start of preheating compressor 24 hours
1.1.2. Cold Storage Technical Specifications:
1.1.2.1. Cold storage room construction
1.1.2.1.1. Floor, wall & roof construction
1.1.2.1.1.1. PPGI G300 Z275 0.5 mm sandwich panel – off white (both sides)*
1.1.2.1.1.2. Insulator panel thickness : 100 mm*
1.1.2.1.1.3. Insulator : polyurethane foam density 45 kg/m3 (+ 5%)*
1.1.2.1.1.4. Joint system: full knock down cam lock
1.1.2.1.1.5. Sandwich panel arrangement: male & female groove
1.1.2.1.1.6. Top layer of floor: aluminum bordes 2 mm
2.1. Utilities / Support Cold Storage Room(*Provided by Buyer)
2.1.1. Building / Civil Construction
Building/civil construction needed to putcold storage room and refrigeration compressor support machine
2.1.1. Cold storage area requirement : W xW X H = 3,500 x 3,500 x 2,700 mm
2.1.1.1 Cast / ceramic floor K-100 to K 150(*provided by the buyer) (*optional 1)
2.1.1.2 Sandwich panel floor 100 mm thick(*provided by supplier) (*optional 2)
2.1.1.3 Machine bottom construction : UNPcarbon steel finish paint
2.1.1.4 top construction of the machine :gloss ss box pipe.
2.1.2. Electricity
Electricity is needed to drive motors,compressors and electrical systems in cold storage
2.1.1. Cold storage electricity needs;
3.1.2.1.1. Compressor 1 stage : 3 HP (2,250Watt / 380V / 3 phase
3.1.2.1.2. Evaporator heater + fan : 100Watt / 380 V / 3 phase
3.1.2.1.3. Condenser fan : 100 Watt / 380 V/ 3 phase
3.1.2.1.4. Total electricity demand: estimate 2.750 Watt / 380 V / 3 phase
Notes :
- Prices in Hundreds of Millions (DP Prices Only)
- The goods are made first (if there are ready, must see the goods in the workshop first).
- Prices do not include postage (postage listed is for sending purchase documents)
- Preferably chat to the number listed in the picture of the item
- A visit to the workshop is required before making a transaction. (Due to the large value). - The price listed is only for the unit of goods (not including installation costs for technicians, accommodation and transportation for installation technicians)