Air Blast Freezer Capacity 0.9 Ton
Description:
1.1. Technical Specifications & AirBlast Freezer Support
1.1.1. Air Blast Freezer (ABF)Air blastfreezer is a cooling machine unit designed for a functioning freezing process prosesas follows :
- Prevents reduced fluid content
- Prevents discoloration and taste Preventsthe proliferation of freezing bacteriafast
- The initial temperature of the materialis + 30°C, frozen to -38°C within 8 hours
1.1.1.1. Room dimensions (Outside): W x W xH = 2,400 x 1,800 x 2,300 mm
1.1.1.2. Capacity : 0.9 ton
1.1.1.3. Blast time: 8 hours
1.1.1.4. Refigerant : Freon R404 or R22
1.1.1.5. Room temperature : -38 to -45°C
1.1.1.6. Lighting system: water proof TLlamp
1.1.1.7. Automatic control
1.1.1.8. Air blast freezer cooling airsystem:
1.1.1.8.1. Compressor type semi hermetic 2stage
1.1.1.8.2. Air cooler evaporator
1.1.1.8.3. Air cooler condenser
1.1.1.9. Construction of air blast freezerroom:
1.1.1.9.1. Wall & roof construction :Sandwich Panel PPGI G300 Z275 0.5 mm off - white
1.1.1.9.2. Floor construction : PPGI G300Z275 0.5 mm sandwich panel + Aluminumlanding 2 mm
1.1.1.9.3. Insulator: 150 mm thickpolyurethane foam (density 45 kg/m3)1.1.1.9.4. Knock down system with cam-lock lock (iron & plastic)1.1.1.9.5. Swing door with Heavy duty Hinge & safety lock system
1.1.1.9.6. Door size: 1000 mm x 2000 mm
1.1.1.9.7. Plastic curtain over lapping 20%​​of the door size.
1.1.1.10.1 Compressor 2 stage : 8 HP (6.000Watt)/ 380 V / 3 Phase
1.1.1.10.2 Evaporator Fan & Heater : (2x375watts)+ 500 watts / 380 V / 3 Phase
1.1.1.10.3Fan Condenser : 375 watt / 380 V / 3 Phase
1.1.1.10.4Total electricity demand (estimated): 7,625watts / 380 V / 3 Phase
2.1. Utilities / Support Air Blast Freezer Room
2.1.1. Building / Civil Construction
Building/civil construction needed to putair blast freezer room and machine supportrefrigeration compressor
2.1.1.1 Required area of ​​air blastfreezer room : W x W X H = 3,500 x 2,500 x 3,000 mm
2.1.1.2 Refrigeration unit area requirementW x W x H : 2,000 x 3,000 x 3000 mm
2.1.2. Electricity
Electricity is needed to drive motors,compressors and electrical systems in cold storage
2.1.2.1 Electricity requirement for airblast freezer room (estimated): 7,625 KW/380V/3 phase
Notes : - Prices in Hundreds of Millions (DP Prices Only)
- The goods are made first (if there are ready, must see the goods in the workshop first). - Prices do not include postage (postage listed is for sending purchase documents)
- Preferably chat to the number listed in the picture of the item - A visit to the workshop is required before making a transaction. (Due to the large value).
- The price listed is only for the unit of goods (not including installation costs for technicians, accommodation and transportation for installation technicians)